POWER ELECTRONICS
POWER CONNECTIONS
61
Recommended Cable Section
Model
Screw
Torque
[1]
[Kgf * cm /
Nm]
Wire
[2]
mm²
AWG
R, S, T
U, V, W
R, S, T
U, V, W
230V
1-phase
0.4 kW
M3.5
(1/8“)
2.1 ~ 6.1 /
0.2 ~ 0.6
2
2
14
14
0.75 kW
1.5 kW
2.2 kW
M4 (1/8“)
3.5
3.5
12
12
230V
3-phase
0.4 kW
M3.5
(1/8“)
2
2
14
14
0.75 kW
1.5 kW
2.2 kW
3.7 kW
M4 (1/8“)
3.5
3.5
12
12
4 kW
5.5 kW
6
6
10
10
7.5 kW
11 kW
M5
(3/16“)
4.0 ~ 10.2 /
0.4 ~ 1.0
10
10
8
8
15 kW
16
16
6
6
400V
3-phase
0.4 kW
M3.5
(1/8“)
2.1 ~ 6.1 /
0.2 ~ 0.6
2
2
14
14
0.75 kW
1.5 kW
2.2 kW
3.7 kW
M4 (1/8“)
4 kW
5.5 kW
2.5
2.5
14
14
7.5 kW
4
4
12
12
11 kW
M5
(3/16“)
4.0 ~ 10.2 /
0.4 ~ 1.0
15 kW
6
6
10
10
18.5 kW
10
10
8
8
22 kW
[
1
] Use only the specified torque on the screws, otherwise damage could occur. Loose