POWER ELECTRONICS
POWER CONNECTIONS
69
Short Circuit
The following table shows the voltage and current ratings for fuses and
circuit breakers.
Model
AC Input Fuse
AC Reactor
DC Reactor
Current
[A]
Voltage
[V]
Inductance [mH]
Current
[A]
Inductance [mH]
Current
[A]
230V
1-phase
0.4 kW
10
600
1.2
10
4
8.67
0.75 kW
1.5 kW
2.2 kW
0.4 kW
15
0.88
14
3
13.05
20
0.56
20
1.3
18.45
230V
3-phase
10
1.2
10
4
8.67
0.75 kW
1.5 kW
2.2 kW
3.7 kW
4 kW
15
0.88
14
3
13.05
20
0.56
20
1.33
18.45
32
0.39
30
26.35
50
5.5 kW
50
0.3
34
1.6
32
7.5 kW
63
0.22
45
1.25
43
11 kW
15 kW
0.4 kW
80
0.16
64
0.95
61
100
0.13
79
0.7
75
400V
3-phase
10
4.81
4.8
16
4.27
0.75 kW
1.5 kW
2.2 kW
3.7 kW
3.23
7.5
12
6.41
15
2.34
10
8
8.9
20
1.22
15
5.4
13.2
4 kW
32
5.5 kW
1.12
19
3.2
17
7.5 kW
11 kW
15 kW
35
0.78
27
2.5
25
50
0.59
35
1.9
32
63
0.46
44
1.4
41
18.5 kW
70
0.4
52
1
49
22 kW
100
0.3
68
0.7
64

Table of Contents