Section V Parameter Function Table
30
Scurve stop time at the
acceleration step
Scurve start time at the
deceleration step
Scurve stop time at the
deceleration step
1 Indicate that the slope of the output frequency from 0 to the max.
2 Indicate that the slope of the output frequency at constant segment.
3 Indicate that the slope of the output frequency is reduced to 0 from the max.
Such as setting the S curve acceleration and deceleration, acceleration and deceleration time
from 0Hz to the maximum frequency is calculated as follows:
Plus acceleration S characteristic time = F09 * F20
Constant extra acceleration S characteristic time = F09-(F09 * F20 + F09 * F21)
Minus acceleration S characteristic time = F09 * F21
Full acceleration time = F09 Acceleration time
Velocity S addition and subtraction characteristic time = F10 * F22
Constant deceleration S characteristics time = F10-(F10 * F22 + F10 * F23)
And reduction rate of S characteristic time = F10 * F23
All deceleration time = F10 deceleration time
F20 F21 F22 F23
1 12
3
2
3
F09
F10
Target frequency
running time
Current frequency
S curve acceleration&deceleration
V/F control slip
compensation
Slip compensation invalid
Valid only under V/F control mode.
0 : Slip compensation function is invalid.
1 : Slip compensation function is valid.
Slip compensation value adjusted by the following parameters to ensure stable speed under
load fluctuations and heavy load,
C09 Low Slip Gain
C10 Low Slip switching frequency
C11 High-Speed Slip Gain
Slip C12 high-speed switching frequency
Minimum running
frequency
The set frequency lower than the minimum running frequency, the converter will stop, that
is, when the set frequency is less than the minimum running frequency, are determined that the
set frequency is 0.
Minimum running frequency" and "lower frequency" relationship is as follows.