7.4 Inverter settings
Using the tables below set the listed parameters. Once complete, run the inverter at the various
required speeds and acceleration/deceleration profiles. Ensure smooth movement throughout the
speed range.
7.4.1 Film Feed Inverter
S520-0.2Kw Film Feed Inverter
No.
Description
Range
Unit
Setting
Setting
1
Upper limit frequency used for the normal
running of film feed motor
0-120 Hz
0.1 Hz 120 Hz 50 Hz
Multi speed 3 0-120 Hz
0.1 Hz 50Hz 5Hz
7
Acceleration time
0-999
Sec
0.1 Hz 5.0 Sec
0.4 Sec
8
Deceleration Time
0-999
Sec
0.1 Hz 5.0 Sec
0.4 Sec
8
Deceleration Time (registered film)
0-999
Sec
0.1 Hz 5.0 Sec
0.2 Sec
9
Thermal overload
0-15
Amps
0.1A
Rated
Current
0.8 A