46 WiNG-MGR User Guide 800.518.1519
3 Web Interface
Parity Selectable: None, Even, Odd
Default: None
BACnet / MSTP
Watchdog
If the WiNG-MGR loses BACnet communications, you can program
the WiNG-MGR to automatically attempt to restore communications.
The WiNG-MGR must detect a period of inactivity on the port before
it can reset or reboot anything - this help avoid executing a reboot
while someone is performing maintenance on or configuring a unit.
Reset MSTP Port - The WiNG-MGR will reset the MSTP port once it
detects no activity on the port for two minutes.
System Reboot - The WiNG-MGR will reboot itself once it detects no
activity on the MSTP port for fifteen minutes.
Default: Disabled
Option Description
Table 3.10
EIA-485 Configuration Options