rletech.com WiNG-MGR User Guide 97
D Troubleshooting
D.2. Sensor Troubleshooting
The WiNG-MGR is designed to work with a RLE Technologies’ WiNG sensors. Sometimes,
problems may occur with the sensors that affect the way they interact with the WiNG-MGR.
Use the following guidelines to troubleshoot WiNG sensors.
The sensor does not seem to be working. It may have a battery problem.
Check the battery’s voltage if the sensor begins to show inconsistent or unreliable results. As
battery power degrades, the sensor may report data outside the bounds of reasonable readings.
If this occurs, replace the battery.
When you replace the battery, replace it with a 3.6V lithium battery, NOT a standard alkaline
AA cell. Also make sure you replace it with the terminals facing the correct direction. The
sensor will not function with an alkaline cell or if the battery is inserted backwards.

Table of Contents