rletech.com WiNG-MGR User Guide 59
3 Web Interface
Logged Points Temperature logging can be seen on each sensor’s individual sensor
page. Use this option to determine how frequently the sensors are
sampled for graphing and logging purposes.
Default: Temperature or Analog - 5 Minute
Log Data Range The WiNG-MGR will log temperature readings that fall within a
designated range. Readings that fall outside the range will be
omitted. Select the range that best suits your application.
Default: 127 to -128 degrees
Battery Meter Type A battery meter can be displayed for each individual sensor. Use this
dropdown menu to determine if the battery reading will be displayed,
and if it will be displayed as voltage or run hours.
Default: Voltage
Low Battery Alarm If you’re monitoring the battery voltage reading, you need to assign a
voltage threshold for the low battery alarm. Assign that here.
Default: 2.7 Volts
Sensor CSV File
Upload Sensor CSV Upload a CSV file to configure sensors in mass on this unit. This
feature is particularly helpful if you are configuring multiple identical
WiNG-MGR systems simultaneously.
Download Sensor
CSV File
Download a CSV file that shows all sensors configured in the
Wi-MGR.
Delete Sensors
Delete Sensor
Range
If you wish to delete some sensors monitored by the WiNG-MGR
without deleting all the sensors, use this option. Enter the range of
sensors you wish to delete, and click the Delete button. If you wish to
delete one specific sensor, enter that sensor’s number as both the
start and end points for the sensor range.
Delete All Sensors This command erases all the information about the sensors the
WiNG-MGR is currently monitoring. Users will have to reinstall
sensor information after the button is clicked, or rediscover sensors
already deployed.
Delete All Sensor
Data Logs
Click this button to delete all logged data for all the sensors
associated with this system.
Attribute Description
Table 3.19
Sensor Configuration Options