86 WiNG-MGR User Guide 800.518.1519
To determine communications objects for sensors past sensor number 20, either refer to the
table and follow the numbering pattern for your sensor number, or use the following formulas.
For example, if you were determining communications objects for sensor number 28:
♦ Modbus Registers are as follows, where the n is replaced with the sensor’s two digit (put
a 0 before a single digit number) sensor number and y is replaced with the sensor’s two
digit (put a 0 before a single digit number) sensor number minus one, so if you were
working with sensor 28 you’d replace n with 28 and y with 27.
– 40y1 = 40271
– 40y2 = 40272
– 40y3 = 40273
– 40y4 = 40274
– 40y6 = 40276
– 40y7 = 40277
– 40y8 = 40278
– 40n0 = 40280
♦ BACnet Instances are as follows, where the n is replaced with the sensor’s sensor
number
– ai: n01 = ai: 2801
– ai: n02 = ai: 2802
– ai: n03 = ai: 2803
–
av: n01 = av: 2801
– av: n02 = av: 2802
♦ SNMP Object Identifiers are as follows, where the last digit, n, is replaced with the
sensor’s sensor number
–
1.3.6.1.4.1.3184.1.15.2.2.1.2.n = 1.3.6.1.4.1.3184.1.15.2.2.1.2.28
– 1.3.6.1.4.1.3184.1.15.2.2.1.3.n = 1.3.6.1.4.1.3184.1.15.2.2.1.3.28
– 1.3.6.1.4.1.3184.1.15.2.2.1.4.n = 1.3.6.1.4.1.3184.1.15.2.2.1.4.28
– 1.3.6.1.4.1.3184.1.15.2.2.1.6.n = 1.3.6.1.4.1.3184.1.15.2.2.1.6.28
– 1.3.6.1.4.1.3184.1.15.2.2.1.7.n = 1.3.6.1.4.1.3184.1.15.2.2.1.7.28
– 1.3.6.1.4.1.3184.1.15.2.2.1.8.n = 1.3.6.1.4.1.3184.1.15.2.2.1.8.28
– 1.3.6.1.4.1.3184.1.15.2.2.1.9.n = 1.3.6.1.4.1.3184.1.15.2.2.1.9.28
– 1.3.6.1.4.1.3184.1.15.2.2.1.10.n = 1.3.6.1.4.1.3184.1.15.2.2.1.10.28
– 1.3.6.1.4.1.3184.1.15.2.2.1.11.n = 1.3.6.1.4.1.3184.1.15.2.2.1.11.28
– 1.3.6.1.4.1.3184.1.15.2.2.1.12.n = 1.3.6.1.4.1.3184.1.15.2.2.1.12.28