124 Rockwell Automation Publication 520-UM001K-EN-E - August 2021
Chapter 3 Programming and Parameters
Advanced Program Group (continued)
A490 [Load Loss Level] Related Parameter(s): A491
PowerFlex 525 only.
Provides a software trip (Load Loss fault) when the current drops below this level for the time specified in A491 [Load Loss Time].
Values
Default: 0.0 A
Min/Max: 0.0/Drive Rated Amps
Display: 0.1 A
PF 525
A491 [Load Loss Time] Related Parameter(s): A490
PowerFlex 525 only.
Sets the required time for the current to be below A490 [Load Loss Level] before a Load Loss fault occurs.
Values
Default: 0 s
Min/Max: 0/9999 s
Display: 1 s
PF 525
A492 [Stall Fault Time]
Sets the time that the drive remains in stall mode before a fault is issued.
Options
0“60 Seconds (Default)
1 “120 Seconds”
2 “240 Seconds”
3 “360 Seconds”
4“480 Seconds
5 “Flt Disabled”
A493 [Motor OL Select] Related Parameter(s): P032, P033
Drive provides Class 10 overload protection. Settings 0...2 select the derating factor for the I
2
t overload function.
Options
0“No Derate (Default)
1 “Min. Derate”
2 “Max. Derate”
Min Derate
0
80
100
60
40
20
% of [Motor OL Curent]
No Derate
0
80
100
60
40
20
% of [Motor NP Hertz]
% of [Motor OL Curent]
% of [Motor NP Hertz]
% of [Motor OL Curent]
% of [Motor NP Hertz]
Max Derate
0
80
100
60
40
20
0
200
175
150
125100755025
0
200
175
150
125100755025
0
200
175
150
125100755025
A494 [Motor OL Ret]
Selects whether the motor overload counter is saved on power-down or reset on power-up.
Options
0 “Reset” (Default)
1“Save