Rockwell Automation Publication 520-UM001K-EN-E - August 2021 77
Chapter 3 Programming and Parameters
Basic Display Group (continued)
b007 [Fault 1 Code] Related Parameter(s): F604-F610
b008 [Fault 2 Code]
b009 [Fault 3 Code]
A code that represents a drive fault. Codes appear in these parameters in the order they occur (b007
[Fault 1 Code] = the most recent fault). Repetitive faults are only
recorded once.
See Fault and Diagnostic Group for more information.
Values
Default: Read Only
Min/Max: F0/F127
Display: F0
b010 [Process Display] Related Parameter(s): b001, A481, A482
32 bit parameter.
Output frequency scaled by A481 [Process Disp Lo] and A482 [Process Disp Hi].
Scaled Process Value (PV) = (([Process Disp Hi] - [Process Disp Lo]) x ([Output Freq] - [Minimum Freq])) / ([Maximum Freq] - [Minimum Freq])
Values
Default: Read Only
Min/Max: 0/9999.00
Display: 0.01
32
b011 [Process Fract] Related Parameter(s): b001, A481, A482
Output frequency (fractional portion) scaled by A481 [Process Disp Lo] and A482 [Process Disp Hi].
Scaled Process Value (PV) = (([Process Disp Hi] - [Process Disp Lo]) x ([Output Freq] - [Minimum Freq])) / ([Maximum Freq] - [Minimum Freq])
Values
Default: Read Only
Min/Max: 0.00/0.99
Display: 0.01