Appendix B: Product Certifications
September 2015
227
Product Certifications
IG IECEx FISCO
Certificate: IECExBAS08.0045X
Standards: IEC60079-0:2011, IEC60079-11:2011
Markings: Ex ia IIC T4 Ga (-60 °C
T
a
+60 °C)
Special Conditions for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient
suppressor, it is incapable of withstanding the 500 V
isolation from earth test and this must be taken into
account during installation.
2. The enclosure may be made of aluminum alloy and
given a protective polyurethane paint finish; however
care should be taken to protect it from impact and
abrasion when located in Zone 0.
N7 IECEx Type n
Certificate: IECExBAS08.0046X
Standards: IEC60079-0:2011, IEC60079-15:2010
Markings: Ex nA IIC T4 Gc (-40 °C
T
a
+70 °C)
Special Condition for Safe Use (X):
1. If fitted with a 90 V transient suppressor, the equipment
is not capable of withstanding the 500 V electrical
strength test as defined in clause 6.5.1 of
IEC60079-15:2010. This must be taken into account
during installation.
Brazil
E2 INMETRO Flameproof
Certificate: CEPEL 09.1767X, CEPEL 11.2065X,
UL-BR 14.0375X
Standards: ABNT NBR IEC60079-0:2008,
ABNT NBR IEC60079-1:2009,
ABNT NBR IEC60079-26:2008,
ABNT NBR IEC60529:2009,
ABNT NBR IEC60079-0:2008 + Errata
1:2011, ABNT NBR IEC 60079-1:2009 +
Errata 1:2011, ABNT NBR IEC
60079-26:2008 + Errata 1:2009
Markings: Ex d IIC T6/T5 Ga/Gb IP66,
T6(-50 °C
T
a
+65 °C),
T5(-50 °C
T
a
+80 °C)
Special Conditions for Safe Use (X):
1. The device contains a thin wall diaphragm. Installation,
maintenance and use shall take into account the
environmental conditions to which the diaphragm will
be subjected. The manufacturer’s instructions for
installation and maintenance shall be followed in detail
to assure safety during its expected lifetime.
2. The Ex d blanking elements, cable glands, and wiring
shall be suitable for a temperature of 90 °C.
3. In case of repair, contact the manufacturer for
information on the dimensions of the flameproof joints.
I2 INMETRO Intrinsic Safety
Certificate: CEPEL 09.1768X, CEPEL 11.2066X
Standards: ABNT NBR IEC60079-0:2008,
ABNT NBR IEC60079-11:2009,
ABNT NBR IEC60079-26: 2008,
ABNT NBR IEC60529:2009
Markings: Ex ia IIC T4 Ga IP66W (-60 °C
T
a
+70 °C)
Special Condition for Safe Use (X):
1. If the equipment is fitted with an optional 90 V transient
suppressor, it is not capable of withstanding the 500 V
insulation test required by ABNT NBR IRC
60079-11:2008. This must be taken into account when
installing the equipment.
IB INMETRO FISCO
Certificate: CEPEL 09.1768X, CEPEL 11.2066X
Standards: ABNT NBR IEC60079-0:2008,
ABNT NBR IEC60079-11:2009,
ABNT NBR IEC60079-26: 2008,
ABNT NBR IEC60529:2009
Markings: Ex ia IIC T4 Ga IP66W (-60 °C
T
a
+60 °C)
Table 15. Input Parameters
Parameters
FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
< 5 nF
Inductance L
i
< 10 F
Table 16. Input Parameters
Parameters
HART Fieldbus/PROFIBUS
Voltage U
i
30 V 30 V
Current I
i
200 mA 300 mA
Power P
i
1 W 1.3 W
Capacitance C
i
0.012 F 0 F
Inductance L
i
0 mH 0 mH
Table 17. Input Parameters
Parameters
FISCO
Voltage U
i
17.5 V
Current I
i
380 mA
Power P
i
5.32 W
Capacitance C
i
< 5 nF
Inductance L
i
< 10 F