Reference Manual
00809-0100-4809, Rev DA
Appendix B: Product Certifications
September 2015
224
Product Certifications
Special Conditions for Safe Use (X):
1. When the thread adapter or blanking plug is used with
an enclosure in type of protection increased safety “e”
the entry thread shall be suitably sealed in order to
maintain the ingress protection rating (IP) of the
enclosure.
2. The blanking plug shall not be used with an adapter.
3. Blanking Plug and Threaded Adapter shall be either NPT
or Metric thread forms. G
1
/2 and PG 13.5 thread forms
are only acceptable for existing (legacy) equipment
installations.
Additional Certifications
SBS American Bureau of Shipping (ABS) Type Approval
Certificate: 09-HS446883A-PDA
Intended Use: Measure gauge or absolute pressure of
liquid, gas or vapor applications on ABS
classed vessels, marine, and offshore
installations.
SBV Bureau Veritas (BV) Type Approval
Certificate: 23155
Requirements: Bureau Veritas Rules for the Classification
of Steel Ships
Application: Class notations: AUT-UMS, AUT-CCS,
AUT-PORT and AUT-IMS; Pressure
transmitter type 3051 cannot be
installed on diesel engines
SDN Det Norske Veritas (DNV) Type Approval
Certificate: A-14185
Intended Use: Det Norske Veritas’ Rules for Classification
of Ships, High Speed & Light Craft and Det
Norske Veritas’ Offshore Standards
Application:
SLL Lloyds Register (LR) Type Approval
Certificate: 11/60002
Application: Environmental categories ENV1, ENV2,
ENV3, and ENV5
C5 Custody Transfer - Measurement Canada Accuracy
Approval
Certificate: AG-0226; AG-0454; AG-0477
B.4 Rosemount 2051CFA and
2051CFC_A
Rev 1.0
B.4.1 European Directive Information
A copy of the EC Declaration of Conformity can be found at
the end of the Quick Start Guide. The most recent revision of
the EC Declaration of Conformity can be found at
www.rosemount.com.
B.4.2 Ordinary Location Certification
As standard, the transmitter has been examined and tested to
determine that the design meets the basic electrical,
mechanical, and fire protection requirements by a nationally
recognized test laboratory (NRTL) as accredited by the Federal
Occupational Safety and Health Administration (OSHA).
North America
E5 USA Explosionproof (XP) and Dust-Ignitionproof (DIP)
Certificate: 3032938
Standards: FM Class 3600 – 2011,
FM Class 3615 – 2006,
FM Class 3810 – 2005,
ANSI/NEMA 250 – 1991,
ANSI/IEC 60529 2004
Markings: XP CL I, DIV 1, GP B, C, D; DIP CL II, DIV 1, GP
E, F, G; CL III; T5(-50 °C
T
a
+85 °C); Factory
Sealed; Type 4X
I5 USA Intrinsic Safety (IS) and Nonincendive (NI)
Certificate: 3033457
Standards: FM Class 3600 – 1998,
FM Class 3610 – 2007,
FM Class 3611 – 2004, FM Class 3810 – 2005
Table 9. Conduit Plug Thread Sizes
Thread Identification mark
M20 ⫻ 1.5 M20
1
/2 - 14 NPT
1
/2 NPT
G
1
/2A G
1
/2
Table 10. Thread Adapter Thread Sizes
Male thread Identification mark
M20 ⫻ 1.5 - 6H M20
1
/2 - 14 NPT
1
/2 NPT - 14 NPT
3
/4 - 14 NPT
3
/4 - 14 NPT
Female thread Identification mark
M20 ⫻ 1.5 - 6H M20
1
/2 - 14 NPT
1
/2 NPT - 14 NPT
PG 13.5 PG 13.5
Location classes
Temperature D
Humidity B
Vibration A
EMC B
Enclosure D