EasyManua.ls Logo

Rotax MMH-912 Series - 3.7) Generator coils

Rotax MMH-912 Series
464 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
74-00-00
page 16
July 01/2008
Effectivity 912/914 Series
Edition 1 / Rev. 2
d04353
BRP-Rotax
Maintenance Manual
3.7) Generator coils
See Fig. 74-12.
If the generator does not work, the reason may be a defective or damaged yellow
alternator cable or a defective winding on the 8 alternator coils (3). Disconnect
alternator cables (yellow) and check resistance values.
Measure the resistance with a multimeter. See 74-00-00 sec. 3.12 and
74-00-00 sec. 5.
NOTE: If the value measured corresponds with the values specified, the
cause may be a defective rectifier-regulator.
CAUTION : When performing any of the work described here, ensure that
no foreign objects can enter the ignition unit.
Checking the integrated alternator in operation:
The check of the internal alternator is carried out at idle speed and under load
on a 150 W (0.201 hp) consumer.
Establish check circuit as shown on wiring diagram Fig. 74-12.
Set engine speed to 4000 rpm.
Check that charge indicating lamp goes out.
Read off the idle voltage on the voltmeter (8) and record it in the 74-00-00
sec. 5 „Form sheets“.
Close circuit-breaker (7), read off voltage under load on the voltmeter (8)
and record it in the 74-00-00 sec. 5 „Form sheets“ .
(1) Magneto-generator
(2) Recitfier regulator part no. 965345
(3) Charge indicating lamp 3W (0.004 hp)
(4) Battery 12 V charged
(5) Capacitor 22 000 µF/25 V
(6) Consumer (lamps) 150 W (0.201 hp)
(7) Circuit breaker
(8) Voltmeter
Testing is carried out at 4000 rpm with and without consumer.
GGR+BLC
G
3W
22 000
m
F
150W
+
-
V
A
12V 36Ah
2
1
3
4 5 8
6
7
Fig. 74-12
07539

Table of Contents

Related product manuals