RTK Series 725 Annunciator
65
F9- Non-Critical Group Relay Reflash Function
Group relays are typically used to inform third party devices that there is an alarm within a local
panel, however in the standard mode additional alarms occurring within the same group will not
change the state of the relay if one alarm remains active. The reflash function allows the relay to
change state for 0.5 seconds every time a new alarm occurs within the same group.
FEATURE-F9 STATUS LED
Set channel to disable reflash function on non-critical group relay OFF
Set channel to enable reflash function on non-critical group relay ON
Please note:- Only alarms with function F22 set to on will activate the non critical group relay.
F10- First-Up Sequence FO Or Enable Slow Flash On Non-First Out
Sequences
This feature is used to enable first-up sequence FO on individual channels as required. Full
sequence tables are provided in Section 10
FEATURE-F10 STATUS LED
Set channel to first-up sequence FO not required OFF
Set channel to first-up sequence FO required ON
Please note:- F10 is used to enable slow flash for non first up sequences.
F11- First-Up Sequence F1
This feature is used to enable first-up sequence F1 on individual channels as required. Full sequence
tables are provided in Section 10
FEATURE-F11 STATUS LED
Set channel to first-up sequence F1 not required OFF
Set channel to first-up sequence F1 required ON
F12- First-Up Sequence F2
This feature is used to enable First-Up sequence F2 on individual channels as required. Full
sequence tables are provided in Section 10
FEATURE-F12 STATUS LED
Set channel to first-up sequence F2 not required OFF
Set channel to first-up sequence F2 required ON
F13- First-Up Sequence F3 Or Enable Fast Flash On Non-First Out Sequences
This feature is used to enable first-up sequence F3 on individual channels as required. Full sequence
tables are provided in Section 10
FEATURE-F13 STATUS LED
Set channel to first-up sequence F3 not required OFF
Set channel to first-up sequence F3 required ON
Please note:- F13 is used to enable fast flash for non first out sequences

Table of Contents

Other manuals for RTK 725 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RTK 725 Series and is the answer not in the manual?

RTK 725 Series Specifications

General IconGeneral
BrandRTK
Model725 Series
CategorySecurity System
LanguageEnglish

Related product manuals