EasyManuals Logo
Home>RTK>Security System>725 Series

RTK 725 Series User Manual

RTK 725 Series
95 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #77 background imageLoading...
Page #77 background image
RTK Series 725 Annunciator
77
25. Systems with Serial Communication
Introduction
As an option the annunciator can be supplied with an internal serial communications card which is
switch selectable to use modbus ASCII or modbus RTU protocol . This allows the annunciator to
interface to 3
rd
party devices such as PLC's, DCS, industrial computers, SCADA packages etc. The
annunciator is RS485 / RS422 compatible and can easily be converted to RS232 using a suitable
external converter. As standard the annunciator acts as a 'slave' device, but can be configured to act
as master when communicating to slave P725 annunciators.
Bi-Directional Communications
The bi-directional communications card allows the unit to read and write data to each alarm window,
which provides contact status, window illumination control/status, and pushbutton information. Each
channel within the annunciator can be set to alarm from a hard wired signal input or via the serial
communications as required.
Configuration
The baud rate, parity and protocol are selected by changing DIL switch settings on the
communications card as described later in this section.
Address Selection
Each annunciator is set with a unique address from 0 to 63, which allows up to 64 separate
annunciators to be connected in a single RS485 multi-drop loop. RTK can also supply
comprehensive alarm monitoring and logging software if required.
Character Format
ASCII 7 data, 1 start, 1 stop, 1 parity
RTU 8 data, 1 start, 1 stop, 1 parity
Message Format
In accordance with the standard modbus protocols, all data exchanges are assumed to comply
strictly with these standards. ASCII transmissions will start with a colon and end with longitudinal
redundancy check (LRC), carriage return and line feed. RTU transmissions will not use framing
characters and will incorporate a cyclic redundancy check (CRC).
For further details please refer to the "Modicon modbus protocol reference guide” available from
Modbus-IDA www.modbus.org
Fault Indication
If communications cannot be established within a specified time-out period (typically 10 seconds)
then the watchdog relay on the communications card will trip and, if fitted, the "communications fault"
window will illuminate. This indicates there is a communications fault either with the external device
or with the integral alarm cards within the annunciator. Because the system continually attempts to
regain communications it will self-recover as soon as communication is re-established.

Table of Contents

Other manuals for RTK 725 Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the RTK 725 Series and is the answer not in the manual?

RTK 725 Series Specifications

General IconGeneral
BrandRTK
Model725 Series
CategorySecurity System
LanguageEnglish

Related product manuals