Serial Communications Page 7-
_________________________________________________________________
Multi-drop Mode Though the 2010D's serial RS-232 ports do
not normally support multi-drop operation,
with external hardware, they can be made
to enable the transmitter only when a
thecommand with 2010D's address is
recognized. If multi-drop mode is
selected, the 2010D will activate the DTR
line when responding to a command with the
proper address. This, in turn, would
activate a solid-state relay that connects
the 2010D's transmit line. Normally, the
DTR line will remain low, leaving the
transmitter disconnected.
Return Error Code Though not a standard part of the ML
protocol, if error codes are enabled, they
can provide an invaluable diagnostic tool
for troubleshooting communications
problems. When enabled, a two digit
numeric code, terminated by a <CR>
character, will follow the <NAK>. A
listing of possible error codes is
provided on page 20.
Protocol The Model 2010D currently supports three
command protocols: Monitor Labs (ML), Dot
Command and Modbus. Others may be
supported in the future or upon request -
please contact Sabio for details. When a
protocol is selected, all other options
will be pre-set to the standard settings
for that protocol.
Error Checking If the ML protocol is selected, no data
verification will be selected by default,
however it is possible to select data
verification for the ML protocol, even
though it is not a standard feature of the
protocol. The section entitled "Data
Verification Field" on page 7-16
provides more detail on these data
verification methods.
Command Start The start-of-command character. The "@"
symbol is the default for the ML protocol.