16-10 EB 8331-4 EN
Annex A (conguration instructions)
16.10 Blockage
Blockage detection (c51)
The actuator detects a valve blockage by comparing the travel after the torque-dependent
switch has been triggered with the travel measured on initialization. If the comparison shows
that the limit switch was triggered too early, this indicates that there is a valve blockage. A
blockage is indicated on the display by the
icon.
Blockage removal (c52)
WhentheBlockageremovalfunctionisactive,theactuatorstemextendsandretracts1mm
three times at the most in sequence.
Blocking protection (c53)
The blocking protection prevents the valve from seizing up. If the actuator stem is in the
closedposition(0%),itisextendedslightlyandthenmovedbacktotheclosedposition24
hours after it last moved.
Code Description Default Adjustment range
c51 Blockagedetection NO NO (function inactive)
YES (function active)
c52 Blockageremoval NO NO (function inactive)
YES (function active)
c53 Blockingprotection NO NO (function inactive)
YES (function active)
16.11 Travel
Limited travel range (c63)
TheLimitedtravelrangeparameterdeterminesin%howfartheactuatorstemcanmoveat
themaximum.Theratedtravel(c61)actsasthereference.Whenc63=100.0%,thetravel
range is not limited.
Code Description Default Adjustment range
c61 Rated travel mm
u Read only
c63 Limited travel range 100.0% 10.0to100.0%