8-2 EB 8331-4 EN
Operation
8.1.2 Operating level
The operating level is active while the actuator is in the automatic mode. In this level, import-
ant information on the operation is shown, the operating mode is selected and the initializa-
tion started. The other levels are accessible from the operating level.
All the parameters of the operating level as well as fatal and EEPROM errors are listed in the
'Malfunctions' section.
8.1.2.1 Selecting the operating mode
The actuator is normally in automatic mode indicated by the icon (displayed in Code 0 to
3). In automatic mode, the actuator stem follows the input signal according to the functions
setinthecongurationlevel.
In manual mode, the actuator stem moves to the adjusted manual positioning value. An ac-
tive manual mode is indicated in Code 0 by the
icon.
Code Description WE Adjustment range
2 Operating mode AUTO AUTO (automatic mode)
MAN(manualmode)
3 Positioning value (manual mode) – 0.0to100.0%
The positioning value (manual mode) selected in Code 3 must be adjusted by the amount
corresponding to at least half the dead band (adjustable in c67, see the 'Start-up and cong-
uration' section). Otherwise, the actuator stem will not move.
Example: Dead band adjusted to 2.0 % (default setting)
à
The positioning value (manual mode) must be adjusted by at least 1.0% (for example,
moving the actuator stem from 2.2% to 3.2%).
8.1.2.2 Determining the reading direction
Thedisplaycontentscanbeturnedby180°inCode4toadaptthedisplayreadingtothe
actuator's mounting situation.
Code Description WE Adjustment range
4 Reading direction DISP DISP,
DISP
Note