SEA SYSTEMS
INSTALLATION AND USE MANUAL
CONTROL PANEL and PREWIRED SYSTEM STK1
For Electric and Hydraulic Lifts
MSTK12-GB
Rev.01
30/12/05
SETRONIK1 Pagina 53 di 54
6.BASIC TROUBLESHOOTING PROCEDURES
6.1.A
LARMED CARD (ALL LED ON)
If the card is alarmed (ALL leds ON), locate the error code through the PM programmer
(see paragraph 4.6_Error Code Legend);
HIGHLIGHT
If error 9 is displayed (reversed input phases), switch OFF the control panel (QM
set to OFF), reverse 2 input phases and switch the panel ON again.
If the motor jogs in the opposite direction, reverse 2 panel output phases.
6.2.ERRONEUS READOUT OF THE SHAFT SENSORS
Refer to Paragraph 5.2.