EasyManua.ls Logo

SENTRON PAC4200 - Date; Time

SENTRON PAC4200
284 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
142 System Manual, 09/2009, A5E02316180B-02
SUBPERIOD # Number of subperiods
Range: 1 to 5
Default value: 1
The number "1" defines the fixed block method.
The numbers "2" to "5" define the rolling block method.
SYNC. SOURCE Source of the synchronization pulse for synchronizing the load
profile recording.
Range: NONE, BUS, DIG. INPUT, INT. CLOCK
NONE Synchronization is switched off.
BUS Synchronization via the
communication interfaces.
DIG. INPUT Synchronization via the digital
input.
INT. CLOCK Synchronization via the internal
clock.
Default value: INT. CLOCK
For synchronization via the digital input, the digital input must
previously be parameterized for this purpose. ("SETTINGS >
INTEGRATED I/O > DIGITAL INPUT", Field "ACTION", value
"DEMAND SYNC"). The "SYNC. SOURCE" field is
automatically reset to "NONE" if another function is assigned
to the digital input.
See also
Load profile (Page 33)
9.2.6 Date / time
Device settings relating to the date and time.
Call: "SETTINGS > DATE/TIME"
Figure 9-6 "DATE/TIME" device settings

Table of Contents