Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
System Manual, 09/2009, A5E02316180B-02
151
TIME UNTIL DIMMED Time after which the device switches the backlighting
from "BACKLIGHT LEVEL" to "BACKLIGHT DIMMED.
Range: 0 to 99 min.
Default: 3 min.
INVERT DISPLAY Inversion of the basic representation of the display.
ON/OFF switch:
ON / OFF.
OFF: Light text on dark background.
On: Dark text on light background.
Default:
On:
REFRESH TIME Refresh rate of the display.
Range: 330 to 3000 ms
Default: 330 ms.
The tolerance of the refresh rate is 100 ms.
DISPLAY TEST Screen for testing the functional capability of the display.
Key F3 inverts the test screen.
Key F4 closes the display.
9.2.10 Advanced
Call: "SETTINGS > ADVANCED".
Other device settings.
Password protection
Definition of limit values
Definition of the universal counter
Battery change
Minimum/maximum value, counter, and address reset
PASSWORD PROTECTION
You can protect the device settings against write access with a password. The data can be
read without any restrictions.
PASSWORD PROTECTION Switches password protection ON / OFF.
ON: Password protection switched
on
OFF: Password protection switched
off
Default value: Switched off
PASSWORD Four-digit, numeric password.
Default value: 0000