Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
148 System Manual, 09/2009, A5E02316180B-02
MODE The field is available when the action "PULSE INPUT" is selected.
Counting of pulses or edges.
Range:
PULSE: Pulses are counted.
EDGE: Edges are counted.
Default value: PULSE
PULSES PER
UNIT
The field is available when the action "PULSE INPUT" is selected.
Number of pulses that must be received per unit in order for the
counter to be incremented by "1". The reference unit is defined in the
"UNIT" field.
Range: 1 to 999
Default value: 1
EDGES PER
UNIT
The field is available when the action "ENERGY PULSE" is selected.
Number of edges that must be received per unit in order for the
counter to be incremented by "1". The reference unit is defined in the
"UNIT" field.
Range: 1 to 999
Default value: 1
UNIT Visible when the action "PULSE INPUT" is selected.
Unit to be counted when counting the pulses or edges received:
kWh (active energy)
kVARh (reactive energy)
TEXT
"TEXT" stands for a user definable unit, e.g. m
3
/h or pieces. The text
sequence used to name the unit must be defined via the
communication interface. The defined text sequence is displayed in
the "TEXT" field when you select "TEXT".
TEXT Text sequence used to name the unit to be counted. See "UNIT"
field.
TARGET You will find more detailed information in the following table.
RELATED
COUNTER
The associated user-defined pulse counter is displayed here
independently of the action selected.
This function is only available if at least one
SENTRON PAC 4DI/2DO expansion module is plugged into the
SENTRON PAC.