Appendix
A.3 MODBUS
SENTRON PAC4200
244 System Manual, 09/2009, A5E02316180B-02
Offset Number
of
registers
Name Format Unit Value range Access
6259 6 Minimum Total Power Factor (VARn) with
Time
Float + time stamp - - R
6265 6 Minimum Neutral Current with Time Float + time stamp A - R
6271 6 Minimum Total Reactive Power (VARtot)
with Time
Float + time stamp VAR - R
6277 6 Minimum Total Reactive Power (VAR1)
with Time
Float + time stamp VAR - R
6283 6 Min. Sliding Window Demand Voltage a-n
with Time
Float + time stamp V - R
6289 6 Min. Sliding Window Demand Voltage b-n
with Time
Float + time stamp V - R
6295 6 Min. Sliding Window Demand Voltage c-n
with Time
Float + time stamp V - R
6301 6 Min. Sliding Window Demand Voltage a-b
with Time
Float + time stamp V - R
6307 6 Min. Sliding Window Demand Voltage b-c
with Time
Float + time stamp V - R
6313 6 Min. Sliding Window Demand Voltage c-a
with Time
Float + time stamp V - R
6319 6 Min. Sliding Window Demand Current a
with Time
Float + time stamp A - R
6325 6 Min. Sliding Window Demand Current b
with Time
Float + time stamp A - R
6331 6 Min. Sliding Window Demand Current c
with Time
Float + time stamp A - R
6337 6 Min. Sliding Window Demand Apparent
Power a with Time
Float + time stamp VA - R
6343 6 Min. Sliding Window Demand Apparent
Power b with Time
Float + time stamp VA - R
6349 6 Min. Sliding Window Demand Apparent
Power c with Time
Float + time stamp VA - R
6355 6 Min. Sliding Window Demand Active
Power a with Time
Float + time stamp W - R
6361 6 Min. Sliding Window Demand Active
Power b with Time
Float + time stamp W - R
6367 6 Min. Sliding Window Demand Active
Power c with Time
Float + time stamp W - R
6373 6 Min. Sliding Window Demand Reactive
Power a (VARn) with Time
Float + time stamp VAR - R
6379 6 Min. Sliding Window Demand Reactive
Power b (VARn) with Time
Float + time stamp VAR - R
6385 6 Min. Sliding Window Demand Reactive
Power c (VARn) with Time
Float + time stamp VAR - R
6391 6 Min. Sliding Window Demand Total
Reactive Power a (VARtot) with Time
Float + time stamp VAR - R

Table of Contents