Description
3.4 Load profile
SENTRON PAC4200
34 System Manual, 09/2009, A5E02316180B-02
Fixed block method
The load profile data is calculated and stored at the end of each demand period.
'HPDQG
SHULRG
'HPDQGSHULRG
'HPDQGSHULRG
'HPDQGSHULRG
(QGRI
GHPDQGSHULRG
W>PLQ@
 

Figure 3-3 Load profile, fixed block method
Rolling block method
The rolling block method divides the demand period into subperiods. The load profile data is
calculated and stored at the end of each demand period or subperiod.
'HPDQGSHULRG
'HPDQGSHULRG
'HPDQGSHULRG
'HPDQGSHULRG
(QGRI
VXESHULRG
(QGRI
GHPDQGSHULRG
'HPDQGSHULRG
6XESHULRGV
W>PLQ@
    


Figure 3-4 Load profile, rolling block method
Parameterizing the fixed block and rolling block methods
SENTRON PAC4200 supports the fixed block method as a special case of the rolling block
method. The most important distinguishing feature is the number of subperiods.
Number of subperiods:
The demand period can be divided into a maximum of five subperiods.
The number "1" defines the fixed block method. In this case, the length of the subperiod
is identical to the length of the demand period.
The numbers "2" to "5" define the rolling block method.