EasyManua.ls Logo

Sharp MX-M700N - Page 126

Sharp MX-M700N
412 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MX-M700N SIMULATION 7 – 32
41
41-1
Purpose
Operation test/Check
Function (Purpose)
Used to check the operation of the docu-
ment size sensor and the related circuit.
(The operation of the document size sensor
can be monitored with the LCD display.)
Section
Others
Operation/Procedure
The sensor and detector operation conditions are displayed.
The active sensors and detectors are highlighted.
41-2
Purpose
Adjustment
Function (Purpose)
Used to adjust the document size sensor
sensing level.
Section
Others
Operation/Procedure
1) Open the original cover. With nothing placed on the original
table, select NO ORIGINAL with 10-key.
2) Press the [START] key.
The sensor level is set without document on the document
table.
3) Place an A3 (11x17) document on the document table, and
select A3 ORIGINAL with 10-key.
4) Press the [START] key.
The sensor level is set when detection the document.
If the above procedures are not completed normally, "ERROR"
is displayed. If completed normally, "COMPLETE" is displayed.
41-3
Purpose
Operation test/Check
Function (Purpose)
Used to check the operation of the docu-
ment size sensor and the related circuit.
(The document size sensor output level can
be monitored with the LCD display.)
Section
Others
Operation/Procedure
The detection output level (A/D value) of the document sensors
(PD1 - PD7) is displayed in real time.
* The value in [ ] on the side of each sensor name indicates the
threshold value.
The light receiving value (A/D value) and the threshold value (A/D
value) of PD1 - PD7 are in the range of 1 - 255. The default of
threshold value is 128.
43
43-1
Purpose
Setting
Function (Purpose)
Used to set the fusing temperature in each
operation mode.
Section
Fusing
Operation/Procedure
1) Select the number corresponding to the setting mode with 10-
key.
2) Press the [START] key.
3) Enter the setting value with 10-key.
4) Press the [START] key.
OCSW Document cover status Open: Normal display
Close: Highlighted
PD1 - 7 Document detection sensor
status
No document: Normal
display
Document present:
Highlighted
SIMULATION 41-1
PD SENSOR CHECK..
OCSW PD1 PD2 PD3 PD4 PD5 PD6 PD7
SIMULATION 41-2
PD SENSOR ADJUSTMENT. SELECT1-2, AND PRESS START.
(PLEASE OPEN THE ORIGINAL COVER.)
1. NO ORIGINAL
2. A3 ORIGINAL
1
OCSW Original cover status Open: Normal display
Close: Highlighted
PD1 - 7 PD sensor detection level The value in [ ] indicates the
adjustment threshold value (SIM41-2 adjustment
value).
100V 200V
1 INSIDE NORMAL Fusing roller inside/
normal mode
200 205
2 OUTSIDE
NORMAL
Fusing roller outside/
normal mode
3INSIDE
PREHEAT
Fusing roller inside/
preheat mode
170 170
4 OUTSIDE
PREHEAT
Fusing roller outside/
preheat mode
5 LEFT NORMAL Sub-heat roller/normal
mode
200 205
6 LEFT PREHEAT Sub-heat roller/
preheat mode
170 170
SIMULATION 41-3
PD SENSOR DATA DISPLAY.
OCSW
PD1[128]: 200 PD2[128]: 200
PD3[128]: 50 PD4[128]: 52
PD5[128]: 51 PD6[128]: 50
PD7[128]: 52
1
SIMULATION 43-1
1
FUSER TEMPERATURE SET. SELECT 1-6, AND PRESS START.
1. INSIDE NORMAL 185 5. LEFT NORMAL 185
2. OUTSIDE NORMAL 185 6. LEFT PREHEAT 140
3. INSIDE PREHEAT 140
4. OUTSIDE PREHEAT 140
: '07 Feb 15
1

Table of Contents

Related product manuals