6. Table of D/L Checkup 
●  Table of D/L checkup 
1. LED Lamp in MODEM   
2.  Is  RX-LEVEL  and  SQ   
fitted to the standard? 
   
RX-LEVEL : – 10dB ~ -7dB 
SQ : Over 7 
Naked Eye Test. 
1.  RX-LEVEL  is  fitted  to  the 
standard, TX-LEVEL is adjusted 
from the opposite mode.   
2.  If  SQ  is  low,  check-up 
modem circuit. 
1.  Any  noise  or  rotation  in 
cooling fan in the back side 
of POWER? 
2.  Heat  generating  in 
POWER? 
Naked eye test / Touching   
1. If rotation is abnormal owing 
to some kind of foreign body or 
dirt  is  inserted  in  cooling  fan, 
clean with air.   
2.  After  expediency,  fan  is  still 
malfunction, request A/S.   
Check  9-pin  RS-232 
Connector  or  25-pin 
connector  of  modem  are 
installed loosened.   
Naked eye test 
 
1. Fasten it using driver.   
D/L  is  in  normal  operation 
but  LCD  screen  is  not 
displayed? 
Naked eye test 
1.  Check  LCD  replace  cycle, 
and request A/S if necessary.   
Disassemble  D/L  and  clean 
inside with air.   
1. Check temperature where 
D/L is installed.   
Temp. : 0℃  ~ 70℃ 
1. Operate heater in winter, and 
cooler in summer.   
1.  Guarantee  Back-up  time 
of  UPS  according  to 
environmental regulations. 
2.  Check  by-pass  mode 
Set-up.   
1.  In  case  Back-up  time 
doesn’ t  fit  to  the  regulation, 
check  UPS  battery  and  replace 
it accordingly.   
2.  Set-up  UPS  as  Inverter 
Mode.   
 
●  With good observation of the above rules, you could use D/L more safe.