Field Value
Product type 101
Product code
•
micr
oScan3 Core – EtherNet/IP™: 10768
•
microScan3 Pro – EtherNet/IP™: 10770
Major revision 1
Minor revision Depending on the functionality of the device, see "V
ersion
numbers and functional scope", page 166
Electronic keying According to need:
•
Exact match: major revision and minor revision must be
identical in the configuration and in the device.
•
Compatible module: the major revision must be identical
in the configuration and in the device. The minor revi‐
sion in the device must be greater than or the same as
the minor revision in the configuration.
The Minor Revision may be larger on newer units than on
older units. The Compatible Module setting allows the control‐
ler configuration to remain unchanged when a device is
replaced with a newer device.
Input data Safety
Output data Safety
Data format Integer SINT
Table 7: Connection parameters, assembly data
Field Input assembly
instanc
e
Output assembly
instance
Size (in 8-bit
words)
Safety input (from the view
of t
he control)
Dependent on
assembly used:
•
110
OR
•
113
1278 Dependent on
assembly used:
•
Assembly 110:
8
•
Assembly 113:
16
Safety output (from the view
of t
he control)
1278 Dependent on
assembly used:
•
100
OR
•
103
Dependent on
assembly used:
•
Assembly 100:
8
•
Assembly 103:
16
Configuration assembly
ins
tance
1278
6. Define the connection as a unicast connection over EtherNet/IP or as a multicast
connec
tion over EtherNet/IP.
7. Set the parameters for safety.
Table 8: Safety parameters
Field Value
Input (from the view of the control)
1)
Requested packet interval
(R
PI)
5ms (or a multiple of this)
(Useful in many cases: 10ms. Smaller values make net‐
work transmission more prone to errors. Larger values lead
to longer response times.)
Timeout multiplier Depending on the network, the required response times
and t
he required availability
4 PROJECT PLANNING
70
O P E R A T I N G I N S T R U C T I O N S | microScan3 – EtherNet/IP™ 8020200/1NTM/2024-06-03 | SICK