3UG4.1 line monitoring relay
6.3 3UG4512 line monitoring relay
3UG4 / 3RR2 monitoring relays
118 Manual, 05/2016, NEB927043002000/RS-AC/004
3UG4512-.....
Degree of pollution
3
Ambient temperature
during operating
°C
-25+60
during storage
°C
-40+85
during transport
°C
-40+85
Galvanic isolation
between entrance and outlet
Yes
between the outputs
Yes
between the voltage supply and other
circuits
Yes
Mechanical operating cycles as operating time
typical
10 000 000
Electrical operating cycles as operating time
at
AC-15 at 230 V typical
100 000
Operating cycles with 3RT2 contactor maximum
1/h
5 000

Table of Contents