3UG4625 residual current monitoring relay with 3UL23 transformer
8.7 Technical data
3UG4 / 3RR2 monitoring relays
210 Manual, 05/2016, NEB927043002000/RS-AC/004
3UG4625-.....
Electrostatic discharge
according to IEC 61000-4-2
4 kV contact discharge /
8 kV air discharge
Field-bound parasitic coupling according to IEC 61000-4-3
10 V/m
Thermal current
of the contact-affected switching element
maximum
A 5
Insulation voltage
for overvoltage category III according
to IEC 60664 with degree of pollution 3 rated value
V 300
Degree of pollution
3
Ambient temperature
during operating
°C
-25+60
during storage
°C
-40+85
during transport
°C
-40+85
Design of the electrical isolation
galvanic
Galvanic isolation
between entrance and outlet
Yes
between the outputs
Yes
between the voltage supply and other circuits
No
Mechanical operating cycles as operating time typical
10 000 000
Electrical operating cycles as operating time
at AC-15
at
230 V typical
100 000
Operating cycles with 3RT2 contactor maximum
1/h
5 000