Line connection and line-side power components
3.9 Active Interface Modules internal air cooling
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
119
WARNING
Danger to life through electric shock due to unconnected cable shields
Hazardous touch voltages can occur through capacitive cross-coupling due to unconnected
cable shields.
As a minimum, connect cable shields and the cores of power cables that are not used
(e.g. brake cores) at both ends at the grounded housing potential.
NOTICE
Damage caused by overheating as a result of an inadmissible mounting position
If the Active Interface Module is not operated in a vertical position with the line supply
terminals at the bottom, then the component can be damaged.
Only operate the Active Interface Module in a vertical position with the line connection at
the bottom.
Note
Functional disturbances as a result of line supply disturbances
The devices have b
een tested for standard line supplies according to EN 61800-3. For line
supplies with significant disturbances (e.g. THD > 8
%; very high percentage of switching
peaks in the range >1
kV), the filter of the line-up can be overloaded as a result of the
addi
tional filter power.
Decouple the drive line-ups using suitable measures:
Using a Basic Line Filter
Use an HFD line reactor with damping resistor instead of an Active Interface Module