EasyManua.ls Logo

Siemens 6SL3120-2TE21-0AA3

Siemens 6SL3120-2TE21-0AA3
499 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Motor Modules Booksize
6.3 Motor Module with external air cooling
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
423
Note
If the cooling air requirement is not covered by the filtered fan, the components cannot
output their specified power.
The filters with filter fan must be regularly checked for dirt and cleaned if necessary.
6.3.7
Technical data
6.3.7.1
Single Motor Modules
Table 6- 27 Technical data Single Motor Modules Booksize (3 to 30 A)
External air cooling
6SL3121
1TE13-
0AAx
1)
1TE15-
0AAx
1)
1TE21
0AAx
1)
1TE21
8AAx
1)
1TE23-
0AAx
Output current
Rated current (l
n
)
Base-load current (I
H
)
Intermittent duty current (I
s6
)
40%
Peak current (l
max
)
A
ACrms
A
A
ACrms
A
ACrms
3
2,6
3,5
6
5
4,3
6
10
9
7,7
10
18
18
15,3
24
36
30
25,5
40
56
Output voltage
V
ACrms
0 … 0.717 x DC-link voltage
DC-link current I
d max
A
DC
3,6
6
11
22
36
DC-link voltage
V
DC
510 … 720
DC-link capacitance
μF
110
110
110
220
705
Overvoltage trip
Undervoltage trip
2)
V
DC
V
DC
820 ± 2 %
380 ± 2 %
Electronics power supply
V
DC
24 (20,4 … 28,8)
Electronics current drawn
at 24 VDC
A
DC
0,85
0,85
0,85
0,85
0,8
Current carrying capacity
DC-link busbars
Reinforced DC-link busbars
24 VDC busbars
A
DC
A
DC
A
DC
100
150
20
100
150
20
100
150
20
100
150
20
100
150
20
Unit rating
3)
Based on I
n
(600 VDC; 4 kHz)
Based on I
H
kW
kW
1,6
1,4
2,7
2,3
4,8
4,1
9,7
8,2
16
13,7
Total power loss
(including electronics losses,
see Power loss tables
(Page 781))
W 50,4 73,4 100,4 185,4 309,2
Max. pulse frequency
without derating
with derating
kHz
kHz
4
16
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com