Line Modules Booksize
4.3 Active Line Modules with external air cooling
Booksize Power Units
Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
193
Note
If the cooling air requirement is not covered by the filtered fan, the components cannot
output their specified power.
The filters with filter fan must be regularly checked for dirt and cleaned if necessary.
Table 4- 22 Technical data for Active Line Modules with external air cooling, part 1
7TE25–5AA3
+ Active
Interface
Module
Rated power (S1)
1)
Infeed power (S6 - 40 %)
1)
1)
kW (P
n
)
kW (P
s6
)
max
16
21
36
47
55
71
55
71
Continuous regenerative power
Peak regenerative power
kW
kW
16
35
36
70
55
91
55
Line voltage
Line frequency
V
ACrms
Hz
DC
3 AC 380 … 480 ± 10 % (15 % < 1 min)
47 … 63 Hz
DC link voltage
Overvoltage trip
2)
V
DC
V
DC
DC
510 … 720
820 ± 2 %
Rated input current:
for AC 400 V
Input current:
for AC 380 V / AC 480 V
for AC 400 V; S6 - 40 %
for AC 400 V; peak current
A
AC
A
AC
A
AC
25
26 / 21
32
55
58 /46
71
84
88 / 70
108
84
88 /70
108
Rated DC link current:
for 600 V
DC link current:
for 600 V DC; for S6 - 40 %
for 600 V DC; peak current
A
DC
A
DC
A
DC
27
35
59
60
79
117
92
121
152
92
121
Current carrying capacity
DC link busbars
Reinforced DC link busbars
A
DC
A
DC
100
150
200
--
200
--
200
--
Electronics current drawn
at 24 V DC
A
DC
0,95
1,5
1,9
1,9