Line Modules Booksize
4.3 Active Line Modules with external air cooling
Booksize Power Units
194 Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
7TE25–5AA3
+ Active
Interface
Module
(including electronics losses, see
Power loss tables (Page 781))
W 282,8 666 945,6 945,6
without derating
° C
40
40
40
40
Active Line Module
μF
705
1410
1880
1880
See Section Overcurrent protection using line fuses and circuit
Rated short-circuit current
3)
kA 65 65 65 65
m
3
/h 56 112 160 160
Max. permissible heat sink
temperature
° C 85 90 88 88
Rated voltage for rated data 3 AC 380 V
The specified power ratings apply to the line voltage range from 380 V to 480 V.
Default for 400 V line systems; undervoltage trip threshold is adjusted to the parameterized rated voltage
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
Module in the drive system.
Table 4- 23 Technical data for Active Line Modules with external air cooling, part 2
Rated power (S1)
1)
Infeed power (S6 - 40 %)
1)
1)
kW (P
n
)
kW (P
s6
)
80
106
120
145
Continuous regenerative power
kW
80
120
Line voltage
Line frequency
V
ACrms
Hz
3 AC 380 … 480 ± 10 % (15 % < 1 min)
47 … 63 Hz