Line Modules Booksize
4.6 Basic Line Modules with internal air cooling
Booksize Power Units
246 Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Table 4- 50 Technical data: Basic Line Modules
Rated power (S1)
1)
Infeed power (S6 - 40 %)
1)
1)
kW (P
n
)
kW (P
s6
)
20
26
40
52
100
130
Continuous power
kW (P
n
)
max
5
10
-
Line voltage
Line frequency
V
ACrms
Hz
3 AC 380 … 480 ±10 % (- 15 % < 1 min)
2)
47 … 63
DC link voltage
Overvoltage trip
3)
V
DC
V
DC
DC
480 … 720
820 ± 2 %
Rated input current:
for AC 400 V
Input current:
for AC 380 V / AC 480 V
for AC 400 V; S6 - 40 %
for AC 400 V; peak current
A
AC
A
AC
A
AC
AC
33
35 / 28
43
66
70 / 55
86
166
172 / 138
216
Rated DC link current:
for 600 V
DC link current:
for 540 V
for DC 600 V; S6 - 40 %
for DC 600 V; peak current
A
DC
A
DC
A
DC
33.5
37
43
67
48
87
167
185
217
Current carrying capacity
DC link busbars
Reinforced DC link busbars
A
DC
A
DC
DC
100
150
200
--
200
--
Electronics current drawn at 24 V DC
(including electronics losses, see Power
loss tables (Page 781))
W 144 283.6 628
without derating
° C
40
40
40
Basic Line Module
μF
940
1880
4100
4)
Circuit breaker
(IEC 60947 and UL)
See Section Overcurrent protection using line fuses and circuit
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com