Line Modules Booksize
4.8 Smart Line Modules with internal air cooling
Booksize Power Units
296 Manual, (GH2), 04/2014, 6SL3097-4AC00-0BP6
Smart Line Module
μF
220
330
705
1410
1880
Circuit breaker
(IEC 60947 and UL)
See Section Overcurrent protection using line fuses and circuit breakers
Rated short-circuit current
SCCR
3)
kA 65 65 65 65 65
(internal air
Internal fan
3
Max. permissible heat sink
temperature
° C 69
4)
73
4)
77 80 75
Rated voltage for rated data 3 AC 380 V
The specified power ratings apply to the line voltage range from 380 V to 480 V.
For 16 kW and 36 kW
Smart Line Modules: Default for 400 V line supplies; undervoltage trip threshold is adjusted to the
parameterized rated voltage.
The resulting rated short-circuit current is obtained from the combination of the fuse or circuit breaker – and the Line
Module in the drive system.
4)
Values cannot be read out by the system (STARTER).