Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
130 Manual, 09/2008, A5E02316180B-01
DIGITAL INPUT
Figure 9-7 "DIGITAL INPUT" device settings
DIG.INPUT Digital input
Range:
0.0 Digital input DI0 (terminal labeling)
0.1 Digital input DI1 (terminal labeling)
Default value: 0.0
ACTION Method of using the digital input:
Range:
NONE: The digital input is switched off.
PULSE INPUT: Counting of input pulses.
Note: The universal counter must also be
parameterized for pulse counting. In the
device settings "ADVANCED
> UNIVERSAL COUNTER", set the field
"SOURCE" to the value "DIG. INPUT".
ON/OFF-PEAK: Switching between tariffs. Off-peak if input
active.
TIME SYNC: Synchronization of the internal clock ("Top
of minute").
The internal clock is put forward or back,
depending on whether the time is up to 30
seconds fast or slow.
If a pulse is not received for 20 minutes, an
event is recorded.
DEMAND SYNC: Synchronization of power demand.
STATUS: One event is recorded for each switching
operation.
Default value: NONE
MODE The field is available when the action "PULSE INPUT" is selected.
Counting of pulses or edges.
Range:
PULSE: Pulses are counted.
EDGE: Edges are counted.
Default value: PULSE