Description
3.1 Features
SENTRON PAC4200
18 Manual, 09/2008, A5E02316180B-01
Device versions
The device is available in the following versions:
Table 3- 1 Device versions
SENTRON PAC4200 Power Monitoring Device
Order No. Description
7KM4212-0BA00-2AA0 SENTRON PAC4200 with ring lug terminals
7KM4212-0BA00-3AA0 SENTRON PAC4200 with screw terminals
Measurement
Derivation of more than 300 measured variables from the basic measured variables with
maximum and minimum values (slave pointer function).
At the voltage terminals, SENTRON PAC4200 can be connected direct to 690 V industrial
systems (max. 600 V for Vph, measuring category III, pollution degree 2). Higher voltages
using voltage transformers.
For current transformers x/1 A and x/5 A. Conversion ratio and current direction
programmable.
Can be used in 2-, 3- and 4-wire systems. Suitable for TN, TT and IT systems.
High measuring accuracy: For instance, accuracy class 0.2 in accordance with IEC
61557-12 for the active energy, in other words accuracy equivalent to 0.2% of the
measured value under reference conditions.
Sliding window demand values
Calculation of the sliding window demand values for
Voltages and currents
Power factor per phase and total system
Apparent, active, and reactive power per phase as well as total power
Maximum and minimum values of the sliding window demand with the date and time of
occurrence since startup, the last reset, or the last deletion
Demand calculation for reactive power VAR
1
, reactive power VAR
n
, or total reactive
power VAR
tot
.
Configurable averaging time.
Average values over all phases
Calculation of the average voltage and current values over all phases. The average value
of a three or four-phase system corresponds to the arithmetic mean for the individual
phase values.
Maximum and minimum average values with date and time.