Startup
7.3 Parameterizing the device
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
87
7.3 Parameterizing the device
7.3.1 Procedure
Procedure for parameterizing
To start up the device, you must specify the operating parameters listed below in the device
settings:
Connection type
Voltage
Direct measurement on the system or using voltage transformers
Measuring input voltage in the case of direct measurement on the system
Primary and secondary voltage when measuring using voltage transformers
Current
Primary and secondary current
The following settings are also useful:
Language
Time zone, change to summertime
Password protection
See also
Password management (Page 141)
7.3.2 Language
Setting the language
Set the language in which the display text is to appear.
The available languages are displayed:
at initial startup,
after resetting to factory settings, and
after updating the firmware.