Description
3.16 Events
SENTRON PAC4200
52 Manual, 09/2008, A5E02316180B-01
Table 3- 6 The following events are reported:
Event Event
class
Standard
warning
level
Reason Remedy
START PMD System
information
Information Voltage recovery -
PMD INFO System
information
Warning PMD information Please contact Support.
COMM.FAULT System
information
Warning A communications fault has
occurred at the slot xx interface.
Check the network
settings
FW UPDATE # System
information
Warning Transmission error:
The firmware is not suitable.
Make sure you are using
the correct firmware
version for the update.
Restart the firmware
update.
TIME CORR: System
information
Information Top of minute:
The time has been corrected.
-
TIME SYNC # System
information
Information The time synchronization has
failed.
Interface: Slot xx
The "Top of minute"
pulses for synchronizing
the time are not active.
Check the hardware and
the settings for
transmitting the "Top of
minute" pulses.
VOLTAGE # Operating
information
Warning The supply voltage has been
interrupted.
Measured variable x
The device has been
disconnected from the
network in accordance
with the schedule.
An error has occurred.
Check the power supply.
VOLTAGE
Operating
information
Alarm The voltage is out of range
Measured variable x
CURRENT
Operating
information
Alarm The current is out of range.
Measured variable x
Danger of serious or
fatal injury or of serious
damage to the device.
Make sure the system is
operating under
conditions for which
SENTRON PAC is
approved.
It is possible that the
measurements are not
correctly displayed.
Please contact Support.
LIMIT
Operating
information
Information The upper limit value xxxx has
been exceeded.
Measured variable x, limit
value xxxx
-
LIMIT
Operating
information
Information The lower limit value xxxx has
been exceeded.
Measured variable x, limit
value xxxx
-