Description
3.16 Events
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
53
Event Event
class
Standard
warning
level
Reason Remedy
LIMIT LOG. OP=1 Operating
information
Information The limit logic operation
complies with the limit
value xxxx.
-
TARIFF Operating
information
Information Tariff change to ... -
STATUS DI Operating
information
Information The digital input is activated.
DI address xx.xx
-
STATUS DO Operating
information
Information The digital output is activated.
DO address xx.xx
-
PULSE FREQ
Operating
information
Information The pulse frequency is too high.
DO address xx.xx
-
TIME Operating
information
Information The time was set on:
Slot xx interface
-
FACT. DEFAULTS Operating
information
Information The factory defaults have been
set.
Slot xx interface
-
BASIC PARAM Control Warning The basic configuration has
been changed.
Slot xx interface
-
SETTING Control Warning The configuration has been
changed.
Slot xx interface
-
COMM. Control Information The communication
configuration has been changed.
Slot xx interface
-
MAX/MIN=0 Control Information The maximum / minimum values
have been reset.
Slot xx interface
-
OP.HOURS=0 Control Information The operating hours counter has
been reset.
Slot xx interface
-
D ENERGY=0 Control Information The day energy counter has
been reset.
Slot xx interface
-
EVENT=0 Control Information The event recordings have been
deleted.
Slot xx interface
-
LOAD REC.=0 Control Information The load profile recording has
been deleted.
Slot xx interface
-
ENERGY C.=0 Control Information All energy counters have been
reset.
Value 00000000
Slot xx interface
-