EasyManua.ls Logo

Siemens SENTRON PAC4200 - Voltage Input; Set the Connection Type; Table 7- 2 Available Connection Types

Siemens SENTRON PAC4200
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Startup
7.3 Parameterizing the device
SENTRON PAC4200
90 Manual, 09/2008, A5E02316180B-01
7.3.4 Voltage input
7.3.4.1 Set the connection type
Inform the device of the connection type executed. To do so, enter the short code for the
connection type in the device settings.
Note
Connection type
The connection type executed must agree with the connection type entered in the device!
Table 7- 2 Available connection types
Short code Connection type
3P4W 3 phases, 4 conductors, unbalanced load
3P3W 3 phases, 3 conductors, unbalanced load
3P4WB 3 phases, 4 conductors, balanced load
3P3WB 3 phases, 3 conductors, balanced load
1P2W Single-phase AC
You can find further information on the possible connection types, and on how the measured
value representation depends on the connection type, in the "Description" chapter.
Procedure
1. Exit the measured value display and call the "MAIN MENU":
<F4>
2. In the main menu, go to the "SETTINGS" entry:
<F2>
or <F3>
3. Call the "SETTINGS" entry:
<F4>
4. In the "SETTINGS" menu, go to the "BASIC PARAMETERS" entry:
<F2>
or <F3>
5. Call the "BASIC PARAMETERS" entry:
<F4>
6. In the "BASIC PARAMETERS" menu, call the "VOLTAGE INPUTS" entry:
<F4>
The display shows the currently valid settings.
Figure 7-4 "CONNECTION TYPE" device setting

Table of Contents

Other manuals for Siemens SENTRON PAC4200

Related product manuals