Parameterizing
9.2 Parameterizing the operator interface
SENTRON PAC4200
134 Manual, 09/2008, A5E02316180B-01
(1) Password protection switched OFF
(2)
Password protection switched ON
Figure 9-10 "PASSWORD PROTECTION" device settings
See also
Password protection (Page 49)
Password management (Page 141)
Technical support (Page 12)
LIMITS
Monitoring of up to 12 limit values "LIM0" to "LIM11" and the limit value "LIMIT LOGIC".
The limit value "LIMIT LOGIC" can be made up of any combination of the limit values "LIM0"
to "LIM11" and the digital inputs I0.0 and I0.1.
Left column: Limit designation
Middle column: Monitored data source
Right column: Limit value currently violated:
Yes, No
Figure 9-11 Representation of limit violations
LIM0, LIM1, … LIM11 Limit selection menu. Each limit has the following
properties:
MONITORING Activation of limit monitoring.
ON/OFF switch:
ON / OFF.
ON: Limit monitoring switched on.
OFF: Limit monitoring switched off.
Default value: OFF