Technical data
11.1 Technical data
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
161
Degree of protection and safety class
Protection Class II
Degree of protection according to IEC 60529
Device front IP65
Type 5 enclosure acc. to UL50
Device rear
Device with screw terminal IP20
Device with ring lug terminal IP10
If higher degree of protection requirements are placed on the application engineering, the
customer must take suitable measures
Environmental conditions
Temperature range
Ambient temperature during operation - 10 °C to + 55 °C
Ambient temperature during transport
and storage
- 25 °C to + 70 °C
Relative humidity 95% at 25°C without condensation (normal
conditions)
Site altitude above sea level max. 2000 m
Degree of pollution 2
Environmental tests In accordance with IEC 60068