EasyManua.ls Logo

Siemens SENTRON PAC4200 - Page 199

Siemens SENTRON PAC4200
252 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Appendix
A.3 MODBUS
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
199
Offset Number of
registers
Name Format Unit Value range Access
195 2 Minimum Total Apparent Power Float VA - R
197 2 Minimum Total Active Power Float W - R
199 2 Minimum Total Reactive Power (VARn) Float VAR - R
201 2 Minimum Total Power Factor Float VAR - R
Byte 3 Bit 0 Limit 0
Byte 3 Bit 1 Limit 1
Byte 3 Bit 2 Limit 2
Byte 3 Bit 3 Limit 3
Byte 3 Bit 4 Limit 4
Byte 3 Bit 5 Limit 5
Byte 3 Bit 6 Limit 6
Byte 3 Bit 7 Limit 7
Byte 2 Bit 0 Limit 8
Byte 2 Bit 1 Limit 9
Byte 2 Bit 2 Limit
10
Byte 2 Bit 3 Limit
11
Byte 0 Bit 0 Limit
logic
Byte 0 Bit 1 Logic
result 1 of limits at
inputs 0 ... 3
Byte 0 Bit 2 Logic
result 2 of limits at
inputs 4 ... 7
Byte 0 Bit 3 Logic
result 3 of limits at
inputs 8 ... 11
203 2 Limit Violations* Unsigned long -
Byte 0 Bit 4 Logic
result 4 of limits at
inputs 12 ... 15
R
Byte 0 System
status
Byte 1 Device
status
Byte 2 Device
diagnostics
205 2 PMD Diagnostics and Status* Unsigned long -
Byte 3 Component
diagnostics
R
Byte 3 Bit 0
Output 0
207 2 Digital Outputs* Status Unsigned long -
Byte 3 Bit 1
Output 1
R
Byte 3 Bit 0 Input 0 209 2 Digital Inputs* Status Unsigned long -
Byte 3 Bit 1 Input 1
R

Table of Contents