Appendix
A.3 MODBUS
SENTRON PAC4200
238 Manual, 09/2008, A5E02316180B-01
Offset Number
of
registers
Name Format Unit Applicable
MODBUS
function
codes
Value range Access
0 = 8N2
1 = 8E1
2 = 8O1
63023 2 Format Module
Interface 1
Unsigned
long
-
0x03
0x04
0x10
3 = 8N1
RW
63025 2 Response Time
Module Interface 1
Unsigned
long
ms
0x03
0x04
0x10
0 ... 255 RW
0 = MODBUS R
TU
1 = SEAbus
serial
63033 2 Protocol Module
Interface 2
Unsigned
long
-
0x03
0x04
0x10
2 = Gateway
RW
63035 2 Address Module
Interface 2
Unsigned
long
-
0x03
0x04
0x10
1 ... 247 RW
0 = 4800 baud
1 = 9600 baud
2 = 19
200 baud
63037 2 Baudrate Module
Interface 1
Unsigned
long
-
0x03
0x04
0x10
3 = 38
400 baud
RW
0 = 8N2
1 = 8E1
2 = 8O1
63039 2 Format Module
Interface 2
Unsigned
long
-
0x03
0x04
0x10
3 = 8N1
RW
63041 2 Response Time
Module Interface 1
Unsigned
long
ms
0x03
0x04
0x10
0 ... 255 RW
63043 2 TCP/IP Port
Gateway Module
Interface 1
Unsigned
long
ms
0x03
0x04
0x10
1-ffffh RW
63045 2 TCP/IP Port
Gateway Module
Interface 1
Unsigned
long
ms
0x03
0x04
0x10
1-ffffh RW
63065 2 PROFIBUS ID
PAC4200
Unsigned
long
-
0x03
0x04
8173h R