Description
3.3 Measured variables
SENTRON PAC4200
Manual, 09/2008, A5E02316180B-01
27
Connection type
Measured variable
3P4W 3P3W 3P4WB 3P3WB 1P2W
THD current a ✓ ✓ ✓ ✓ ✓
THD current b ✓ ✓ - - -
THD current c ✓ ✓ - - -
Apparent energy ✓ ✓ ✓ ✓ ✓
Active energy import, export ✓ ✓ ✓ ✓ ✓
Reactive energy import, export ✓ ✓ ✓ ✓ ✓
Unbalance voltage ✓ - - - -
Unbalance current ✓ ✓ - - -
Amplitude unbalance voltage ✓ - - - -
Amplitude unbalance current ✓ ✓ - - -
Distortion current a ✓ ✓ ✓ ✓ ✓
Distortion current b ✓ ✓ - - -
Distortion current c ✓ ✓ - - -
Harmonic content of the 3rd, 5th, 7th, ... 31st harmonics for the a-
n voltage referred to the fundamental
✓ - ✓ - ✓
Harmonic content of the 3rd, 5th, 7th, ... 31st harmonics for the b-
n voltage referred to the fundamental
✓ - - - -
Harmonic content of the 3rd, 5th, 7th, ... 31st harmonics for the c-
n voltage referred to the fundamental
✓ - - - -
Harmonic content of the 3rd, 5th, 7th, ... 31st harmonics for the a-
b voltage referred to the fundamental
✓ ✓ - ✓ -
Harmonic content of the 3rd, 5th, 7th, ... 31st harmonics for the b-
c voltage referred to the fundamental
✓ ✓ - ✓ -
Harmonic content of the 3rd, 5th, 7th, ... 31st harmonics for the c-
a voltage referred to the fundamental
✓ ✓ - ✓ -
Current of the fundamental and current of the 3rd, 5th, 7th, ...
31st harmonics in a
✓ ✓ ✓ ✓ ✓
Current of the fundamental and current of the 3rd, 5th, 7th, ...
31st harmonics in b
✓ ✓ - - -
Current of the fundamental and current of the 3rd, 5th, 7th, ...
31st harmonics in c
✓ ✓ - - -
Universal Counter ✓ ✓ ✓ ✓ ✓
Operating Hours Counter ✓ ✓ ✓ ✓ ✓
1) You can set which type of reactive power (VAR1, VARtot, or VARn) is displayed with the configuration software. All three
reactive power types can be called via the interface.
See also
Connection examples (Page 75)