7 Operation at Use of a PC
7.3 Configuration of the Device
119SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
7.3.3.1.2 Binary Outputs
Default Settings and Setting Ranges of the Binary Outputs
Table 7-4 Settings of Binary Outputs
Parameter Default Setting Setting Range
Source type Indication Indication
Energy counter
Source Type Indication
Indication -none- Acc. to list box
(see Operating Parameters)
Source inverted no no
yes
Operating mode Persistent Persistent
Persistent with fail safe
Pulse
Pulse with retrigger
Output time for pulse operating mode
(setting only possible if operating
modes Pulse and Pulse with retrig-
ger)
20 * 10 ms = 200 ms 50 ms to 3 600 000 ms
Source Type Energy Counter
Energy counter -none- Acc. to list box
(see Operating Parameters)
Energy increase per pulse 1.0 Wh 0.1 Wh/VAh/varh to 1 000 000 Wh/VAh/
varh
Output time for pulse operating mode 20 * 10 ms = 200 ms 50 ms to 3 600 000 ms