7 Operation at Use of a PC
7.6 Example of a Parameterization and Measured Value Evaluation for SENTRON PAC5200
189SENTRON PAC5100/5200, 7KM5212/5412, Device Manual
E50417-H1040-C568-A1, Edition 03.2015
On the Configure tab, Recorder parameters item (see Recorder Parameters), configure the
Measurement recorder with an averaging time of 2 hours and the recorders of average to record all
voltage harmonics.
Figure 7-78 Configure Tab, Recorder Management Example
On the Configure tab, Memory management item (see Memory Management) allocate 50 % of the
storage capacity to the Measurement recorder.
Figure 7-79 Configure Tab, Memory Management Example
Confirm the factory-set report configuration (see Report Configuration).