Configuring the operating system
6.3 Changing settings for operation
Mobile Panel 277 RO
Operating Instructions, 10/2015, A5E36824256-AA
83
Proceed as follows:
1. Touch the "Recalibrate" button to open the following dialog:
2. Briefly touch the middle of the calibration crosshairs
①.
The calibration crosshairs is then displayed at four more positions. Touch the middle of
the calibration crosshairs for each position. If you do not touch the middle of the
calibration crosshairs, the procedure is repeated.
Once you have touched the calibration crosshairs for all positions, the following dialog
appears:
3. Touch the screen within 30 seconds.
The new calibration is saved. If you wait longer than 30 seconds, the new calibration is
discarded and the original calibration remains in effect.
The "OP Properties" dialog , "Touch" tab is displayed again.
4. Close the dialog.
The HMI device touch screen is now recalibrated.