Configuring the operating system
6.7 Communication settings
Mobile Panel 277 RO
98 Operating Instructions, 10/2015, A5E36824256-AA
General information
Note
Changes during the "Transfer" operating mode
If the HMI device is in "Transfer" mode while changes are made to the transfer settings, the
settings only go into effect after the transfer function is restarted.
This may occur if the Control Panel is
opened to change the transfer properties during the
process control phase.
6.7.2
Checking the PROFINET IO settings
The HMI device is supplied with PROFINET IO deactivated. This default setting is necessary
for error-free operation of the HMI device with RemoteOperate.
Requirements
You have opened the "PROFINET" dialog with the "PROFINET" icon.
Check box for enabling or locking the PROFINET IO direct keys
Text box for the device name
MAC address of the HMI device
Procedure
1. Deactivate the "PROFINET IO enabled" check box.
Note
PROFINET IO must be locked. PROFINET IO is not supported by RemoteOperate.
2. Confirm your entries.
The dialog closes.
3. Reboot the HMI device after saving the settings.
Result
PROFINET IO is disabled.